• Xtreme drivers for long life and reliable performance

วิดีโอ

[trigger to render Video Gallery]

รูปภาพ

Specifications Show all

General Information
Application code
EII
Type version
mk1
Lamp type
TL5
Number of lamps
2 piece/unit
Number of products on MCB (16 A type B) (nom.)
12
Automatic restart
Yes
Operating and Electrical
Input voltage
220 to 240 V
Input frequency
50-60 Hz
Operating frequency (min.)
42 kHz
Ignition method
Warm Start
Crest factor (max.)
1.7
Power factor 100% load (nom.)
0.96
Ignition time (max.)
2.0 s
Mains voltage performance (AC)
-8%-+6%
Mains voltage safety (AC)
-10%-+10%
Earth leakage current (nom.)
0.5 mA
Inrush current width
0.310 ms
Constant wattage deviation
-2%/+2%
Ballast factor (nom.)
1.00
Power losses (nom.)
9.5 W
Inrush current peak (max.)
33 A
Wiring
Connector type input terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Cable capacity output wires mutual (nom.)
200 pF
Connector type output terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Wire strip length
8.0-9.0 mm
Input terminal cross section
0.50-1.00 mm²
Output terminal cross section
0.50-1.00 mm²
Auto Insert (ALF/ADS) Wire Cross Section
0.5 mm²
Cable capacity output wires to earth (nom.)
200 pF
System characteristics
Rated ballast-lamp power
54 W
Rated lamp power on TL5
54 W
System power on TL5
63.5 W
Lamp power on TL5
54 W
Power loss on TL5
9.5 W
Temperature
T ambient (max.)
60 °C
T ambient (min.)
-25 °C
T storage (max.)
80 °C
T storage (min.)
-25 °C
T case lifetime (nom.)
75 °C
T-Case maximum (max.)
75 °C
T-Ignition (max.)
60 °C
T-Ignition (min.)
-25 °C
Mechanical and Housing
Housing
L 360x30x28
Emergency Operation
Battery voltage lamp ignition
198 V
Battery voltage lamp operation
176-254
Approval and Application
Energy efficiency index
A2
EMI 9 kHz... 30 MHz
EN55015
EMI 30 MHz... 1,000 MHz
EN55022 level B
Safety standard
IEC 61347-2-3
Performance standard
IEC 60929
Quality standard
ISO 9000:2000
Environmental standard
ISO 14001
Harmonic current emission standard
IEC 61000-3-2
EMC immunity standard
IEC 61547
Vibration standard
IEC68-2-6 F c
Bumps standard
IEC 68-2-29 Eb
Humidity standard
EN 61347-2-3 clause 11
Approval marks
CE marking
ENEC certificate
VDE-EMV certificate
Temperature marking
Yes
Emergency standard
IEC 60598-2-22
Humming and noise level
Inaudible
Product Data
Full product code
871150091431630
Order product name
HF-P Xt 254 TL5 EII 220-240V 50/60Hz
EAN/UPC – product
8711500914316
Order code
913700630066
Numerator – quantity per pack
1
Numerator – packs per outer box
12
Material no. (12NC)
913700630066
Net weight (piece)
0.360 kg